ASCE 7 does not prohibit classificaton of server racks as Dead Load and could be interpretted as specifically permitting it. ASCE 7 Chapter 2 defines "Dead Load" as "Dead loads consist of the weight of all materials of construction incorporated into the building including, but not limited to,...
Thanks Christian for the response. In regards to IEBC triggers for reanalysis, it shouldn't change if the load is classified as dead load or live load. For example: if you design for 2000lb racks - the 5% IEBC triggers means you can put in 2100lb racks without reanalysis - whether the rack is...
Hello Stephan, I don't think I have a satisfying answer, but I tend to agree with the direction you're heading: a project-specific agreement with your owner and AHJ. A safe but conservative approach would be to consider the weight as a sustained SDL for seismic demands but use a LL factor on the...
Ronald, thank you for the response. Agreed that if those unknowns exist then live load is the appropriate classification. For data center projects, SEs work closely with the owner to establish the loading criteria since ASCE7 does not provide a prescribed load for server racks. Specifically,...
Stephen I believe there are a number of reasons that server racks should be considered live, as opposed to dead load. First, they are subject to change in configuration from year to year and from tenant to tenant, as new technology evolves and tenant needs change, resulting in chnage of weight....
Thank you Alex for the response. Is there anyone else from ASCE that can provide a response to my two questions above?
For the four legs of a table on a RCC slab , shall we sure about whether the legs be over Re bar or on concrete alone. Live or dead the load is taking by slab. What's the action of the slab on punching shear. I think it may take a whole year to adjusting the reaction of the slab. It's hardening...
Hi, I have a question regarding classifying server racks (in a data center or office building) as dead load or live load. After a rack is in place, it is typically lifted off of its caster wheels onto 4 leveling legs, anchored as needed in seismic zones, and left in place for at least 3 years....
So, are you saying that the reduced live loads cannot be applied to foundations ?
The reduction is applied because of attractive forces upwards due to planets, but foundation elements experience mostly gravity and some uplifts of water tableEr. Alex Thomas MIE REng CEng M ASCEPP 1000111 000011940940Prof of practice